General Purpose Fans
Click here to download Owners Manual
Click here to download GPX 1611 Drawings
Click here to download GPX 2011 Drawings
Click here to download GPX 2413 Drawings
Click here to download GPX 3013 Drawings
Triangles GPX fans are ruggedly designed for continuous operation for exhausting workshops, barns, poultry houses, greenhouses, garages or anywhere air movement is required to control condensation and reduce the amount of stagnant air. Built in shutters and OSHA compliant guards and standard
Details:
Models | |
---|---|
GPX1611 | 16 inch - GPX General Purpose Fan - 1 Speed, 1/4 HP, Direct Drive, Enclosed Motor, 115 only 1ph, 1650 RPM / Weight: 43 Lbs |
GPX2011 | 20 inch - GPX General Purpose Fan - 1 Speed, 1/4 HP, Direct Drive, Enclosed Motor, 115 only 1ph, 1650 RPM / Weight: 50 Lbs |
GPX2413 | 24 inch - GPX General Purpose Fan - 1 Speed, 1/2 HP, Direct Drive, Enclosed Motor, 115 only 1ph, 1100 RPM / Weight: 66 Lbs |
GPX3013 | 30 inch - GPX General Purpose Fan - 1 Speed, 1/2 HP, Direct Drive, Enclosed Motor, 115 only 1ph, 1100 RPM / Weight: 70 Lbs |
Accessories | |
---|---|
FG12HRTIM | 12 Hour Timer Shipping Weight 1 Lbs |
FG2SWALL | 2 SP Wall Switch Shipping Weight 2lb |
Triangles GPX SERIES FANS are ruggedly designed for continuous operation. They're ideal for workshops, barns, poultry houses, greenhouses, garages or anywhere ventilation is required to control condensation and stagnant air.
Ready to Install is the phrase most associated with the GPX SERIES FANS. Simply cut a square opening in the wall (the size shown below for housing dimension B, plus 1/4 inch). Slide the fan into the opening from the outside of the structure. Fasten the flange securely to your structure. Last, connect motor to a 115 volt , 60 Hz, single phase power source and your fan is ready to exhaust your building. Motors are 115 Volt Totally Enclosed Air Over (TEAO)
GENERAL PURPOSE FANS Specifications: | |||||
---|---|---|---|---|---|
Model No. | Blade Diam. (in) | CFM | RPM | HP | Amps |
GPX1210 | 12 | 1580 | 1625 | 1/6 | 2.2 |
GPX1611 | 16 | 2600 | 1650 | 1/4 | 2.3 |
GPX2011 | 20 | 3200 | 1650 | 1/4 | 2.3 |
GPX2413 | 24 | 5460 | 1100 | 1/2 | 6.2 |
GPX3013 | 30 | 6800 | 1100 | 1/2 | 6.1 |
Preformance shown is for installation type A: free inlet, free outlet. Preformance ratins do not include the effects of accessories. Specifications subject to change without notice. |
Note: Consult the sales department for hazardous location applications.
|
Calculation for Sizing your Fan
For cooling people we suggest 2 to 4 minute single air change
For cooling product we suggest 4 to 6 minute single air change
For removing stagnant air we suggest 6 to 10 minute single air change
Calculation:
A. Building Structure: Length x Width x Ceiling Height = Cubic Feet
B. Decide how many minutes per single air change you require ( 2 thru 10 ) (Note: Your climate or equipment may
alter your minutes required)
C. Divide A by B = Cubic Feet Per Minute (CFM) Air Flow required
Example:
Shipping SPecifications | ||||
---|---|---|---|---|
Model Number | Height | Width | Depth | Weight LBS |
GPX 1210 | 19 inch | 14 inch | 19 inch | 35 |
GPX 1611 | 23 inch | 14 inch | 24 inch | 43 |
GPX 2011 | 27 inch | 14 inch | 28 inch | 55 |
GPX 2413 | 31 inch | 16 inch | 32 inch | 66 |
GPX 3013 | 40 inch | 16 inch | 40 inch | 70 |